SimPowerSystems | ![]() ![]() |
Transient Performance for a Fault at Bus B2
The configuration of the substation circuit breakers normally allows clearing a fault at the bus without losing the lines or the transformers. You now modify your case1
model in order to perform a three-cycle, three-phase-to-ground fault at bus B2:
case1
model. Open the Transformer dialog box. In the Measurements pop-up menu, select Flux and magnetization Current. Open the Multimeter block. Verify that you have six signals available. Select flux and magnetization current on phase A, and click OK.
Waveforms of interest are plotted here:
Figure 2-8: Simulation Results for a 3-Cycle 3-Phase-to-Ground Fault at Bus B2
The 9 Hz subsynchronous mode excited at fault clearing is clearly seen on the phase A voltage at bus B2 (trace 1) and capacitor voltage (trace 3). The 9 Hz voltage component appearing at bus B2 drives the transformer into saturation, as shown on the transformer magnetizing current (trace 4). The flux in phase A of the transformer is plotted on trace 5. At fault application the voltage at transformer terminals drops to zero and the flux stays constant during the fault.
At fault clearing, when the voltage recovers, the transformer is driven into saturation as a result of the flux offset created by the 60 Hz and 9 Hz voltage components. The pulses of the transformer magnetizing current appear when the flux exceeds its saturation level. This current contains a 60 Hz reactive component modulated at 9 Hz.
![]() | Frequency Analysis | Chopper-Fed DC Motor Drive | ![]() |